The adjustable thermal-magnetic trip covers 95 A minimum to 756 A maximum, giving you a wide band to coordinate with downstream loads. Breaking capacity hits 187 kA at 240 V AC, 121 kA at 415/440 V, and still holds 75.6 kA at 500 V — only drops to 3.7 kA at 690 V, so it's a high-interrupting device for most industrial services. A built-in communication function means this breaker can report status and trip events to a higher-level control system — useful for remote monitoring or predictive maintenance on a production line.
Maximum power loss is 4 W. No other measurement function is built in.