Breaking capacity runs 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V — so the same breaker covers both high-fault 240 V distribution and lower-fault 690 V motor circuits without upsizing the frame.
Thermal derating — the real ampacity
Above that it steps down: 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C. If your panel ambient runs 60 °C, plan for 58 A continuous — the 63 A nameplate applies only up to 50 °C.
Dimensions are 105 mm wide, 181 mm high, 86 mm deep — standard 3-pole MCCB footprint for a 160 A frame. The auxiliary contact version is 2 HQ (two changeover contacts), and there is no undervoltage release or voltage trip fitted from the factory.