Siemens 3VA2163-5JQ32-0DC0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2163-5JQ32-0DC0 MCCB, 63 A, 3-Pole, 187 kA at 240

MPN3VA2163-5JQ32-0DC0

SENTRON 3VA2163-5JQ32-0DC0, 3-pole molded case circuit breaker, 63 A, line protection, 187 kA at 240 V, undervoltage release, communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5JQ32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21635JQ320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2163-5JQ32-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-5JQ32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2163-5JQ32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5JQ32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2163-5JQ32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5JQ32-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB with flat derating and high interrupting capacity

The SENTRON 3VA2163-5JQ32-0DC0 is a 3-pole molded case circuit breaker rated 63 A continuous, with a full-scale value of 63 A and an initial trip threshold of 16 A. It carries 187 kA interrupting capacity at 240 V, dropping to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — that last figure tells you this breaker is designed for low-voltage distribution, not 690 V motor circuits. The 63 A rating holds flat from 40 °C through 70 °C, so no derating curve to calculate in a warm panel. It includes an undervoltage release (UVR) and a communication function, plus two auxiliary switches (HQ). The basic switch assembly is order code 3VA21635JQ320AA0.

DIN-rail footprint and panel fit

Mounts on DIN rail. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — that's 4.13 in by 7.13 in by 3.39 in. The 105 mm width is a standard 6-module footprint for this class of MCCB, so it drops into existing panel layouts without re-drilling the backplate. The 86 mm depth leaves room behind the gland plate for the UVR coil wiring and communication cable.

Frequently asked questions

Where can I buy 3VA2163-5JQ32-0DC0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 3VA2163-5JQ32-0DC0's listed depth?

The depth is 86 mm (3.39 in).

What is 3VA2163-5JQ32-0DC0's listed width?

The width is 105 mm (4.13 in).

Will 3VA2163-5JQ32-0DC0 drop into a panel specified around 3VA2163-8JQ32-0AA0 without rewiring?

Both are 3-pole 63 A SENTRON 3VA MCCBs with the same 105 mm width, so they share the same DIN-rail footprint and bus-bar pitch. The 5JQ32-0DC0 includes an undervoltage release and communication function; the 8JQ32-0AA0 may differ in auxiliaries. Check the terminal arrangement and wiring diagram before swapping — the physical fit is the same, but the control wiring may need adjustment.

MPN