Skip to main content
Siemens 3VA2163-5JQ42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5JQ42-0AA0 SENTRON MCCB, 63 A, 4-Pole, ETU56

MPN3VA2163-5JQ42-0AA0
Active

Siemens SENTRON 3VA2163-5JQ42-0AA0, molded case circuit breaker, 4-pole, 63 A, ETU560 electronic trip unit, line protection, breaking capacity 187 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5JQ42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2163-5JQ42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-5JQ42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560

Construction & Connection

3VA2163-5JQ42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5JQ42-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2163-5JQ42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5JQ42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

Integrator's terse spec recap

The Siemens 3VA2163-5JQ42-0AA0 is a SENTRON molded case circuit breaker (MCCB) with 4 poles, rated at 63 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to 70 °C. It carries an ETU560 electronic trip unit, configurable for line protection, with an adjustable N-conductor protection setting (OFF, 40 % to 160 %). Breaking capacity reaches 187 kA at 240 V AC and 121 kA at 415 V and 440 V; at 690 V it still interrupts 3.8 kA. The unit measures 181 mm high, 140 mm wide, and 86 mm deep — a standard MCCB footprint for panel integration.

Panel-builder commissioning notes

Mounts on a DIN rail or panel base; the 86 mm depth fits standard distribution boards. The IP40 front protection means it is suited for indoor panel use where no water jets are present. The ETU560 trip unit supports communication (Communication Function: Yes), allowing integration with higher-level monitoring systems. Power loss is max 4 W, negligible for thermal budget in a populated cabinet. Storage range is -40 °C to 80 °C; operating range -40 °C to 70 °C — the same as the rated current window.

Frequently asked questions

Where can I buy 3VA2163-5JQ42-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ. Submit a request for current pricing and availability.

What are the key ratings of 3VA2163-5JQ42-0AA0?

Rated continuous current 63 A, 4 poles, breaking capacity 187 kA at 240 V and 121 kA at 415 V, ETU560 electronic trip unit.

MPN
3VA2163-5JQ42-0AA0