Siemens 3VA2163-5KP32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5KP32-0BC0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2163-5KP32-0BC0

Siemens SENTRON 3VA2163-5KP32-0BC0, 3-pole molded case circuit breaker, 63 A continuous, 187 kA interrupting at 240 V, undervoltage release, current lifecycle.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5KP32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21635KP320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2163-5KP32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-5KP32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-5KP32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5KP32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2163-5KP32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5KP32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A continuous, no thermal derating through 70 °C

The Siemens SENTRON 3VA2163-5KP32-0BC0 is a 3-pole molded case circuit breaker rated 63 A continuous across the full ambient range from 40 °C to 70 °C — no derating curve to calculate, which simplifies panel thermal coordination. Interrupting capacity hits 187 kA at 240 V, dropping to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V, giving solid fault-level headroom for most industrial distribution boards without needing a current-limiting upstream device.

Built-in undervoltage release, no auxiliary trip module needed

This variant ships with an undervoltage release (UVR) integrated — design of the auxiliary release is listed as undervoltage release (UVR), so you don't need to order a separate shunt trip module for brownout or emergency-stop drop-out schemes. The auxiliary switch complement is 2 auxiliary switches HQ (high-qualified), which gives status feedback without adding a side-mount block. If your BOM calls for ground-fault monitoring, note this unit is specified without that function.

Panel footprint: 105 mm wide, 86 mm deep, 181 mm tall

Dimensions are 105 mm width (4.13 in), 86 mm depth (3.39 in), 181 mm height (7.13 in) — fits the standard SENTRON 3VA2 panel cutout and busbar spacing. The 3-pole form factor matches existing Siemens MCCB mounting rails; no adapter plate needed for most distribution boards. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C, so it handles unheated electrical rooms and outdoor enclosures within reason.

Frequently asked questions

Where can I buy 3VA2163-5KP32-0BC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the interrupting capacity of this MCCB at different voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — sufficient for most industrial distribution fault levels without upstream current-limiting fuses.

Does the 3VA2163-5KP32-0BC0 include an undervoltage release?

Yes, the design of the auxiliary release is an undervoltage release (UVR) — integrated, not a separate add-on module.

What are the physical dimensions of this circuit breaker?

Width 105 mm (4.13 in), depth 86 mm (3.39 in), height 181 mm (7.13 in) — standard 3-pole SENTRON footprint.

MPN
3VA2163-5KP32-0BC0