Its breaking capacity is 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — the voltage on your bus determines which figure governs your SCCR coordination study. The breaker includes a communication function and summation-current ground-fault monitoring on the L-conductor, which means it can report status and detect ground faults without a separate module — useful for coordinated protection schemes in industrial panels.
Dimensions are 181 mm height, 105 mm width, 86 mm depth.