Skip to main content
Siemens 3VA2163-5MN32-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5MN32-0JL0 SENTRON MCCB, 63 A, 3-Pole, Motor

MPN3VA2163-5MN32-0JL0

Siemens SENTRON 3VA2163-5MN32-0JL0, molded case circuit breaker, 3-pole, 63 A, motor protection design, with auxiliary switches and shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5MN32-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21635MN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2163-5MN32-0JL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classE
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-5MN32-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-5MN32-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5MN32-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2163-5MN32-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5MN32-0JL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what it does

The Siemens 3VA2163-5MN32-0JL0 is a SENTRON molded case circuit breaker (MCCB) specifically designed for motor protection, with a continuous current rating of 63 A that holds across the full operating temperature range from -25 °C to 70 °C — no derating needed as the panel warms up. Its interrupting capacity tells you where it can sit in the fault hierarchy: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. That 187 kA at 240 V is high enough for most service-entrance or large-feeder applications; the drop to 3.7 kA at 690 V means it is not intended for 690 V motor circuits without verifying the available fault current. It carries built-in phase failure detection and a trip indicator, plus a voltage-trigger function — useful for signaling a trip condition back to a PLC or annunciator without adding external relays.

Auxiliary configuration and panel integration

This variant ships with the 3VA21635MN320AA0 basic switch and a full auxiliary complement: two auxiliary switches, one trip alarm switch, and one electrical alarm switch, plus a shunt trip (STL) release. That means you get both status feedback and remote tripping capability in one package — no separate add-on modules to order and wire. Footprint is 105 mm wide by 86 mm deep by 181 mm tall, which fits standard MCCB panel cutouts for this class. No undervoltage release, no ground-fault monitoring, and no communication function on this order code — if you need those, look at the 3VA2 family variants with the UVR or COM options.

Lifecycle and sourcing reality

The 63 A rating across the full temperature range and integrated shunt trip suit motor protection duty with a 3-pole footprint.

Frequently asked questions

Does this MCCB include a shunt trip?

Yes, it comes with a shunt trip (STL) auxiliary release factory-installed, plus two auxiliary switches, one trip alarm switch, and one electrical alarm switch.

MPN
3VA2163-5MN32-0JL0