Skip to main content
Siemens 3VA2163-5MN36-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5MN36-0BL0 SENTRON MCCB, 63 A, 3-Pole, Motor

MPN3VA2163-5MN36-0BL0

Siemens SENTRON 3VA2163-5MN36-0BL0, molded case circuit breaker, 3-pole, 63 A, motor protection design, undervoltage release, 2 aux + 1 trip + 1 alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5MN36-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21635MN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2163-5MN36-0BL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classE
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-5MN36-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-5MN36-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5MN36-0BL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2163-5MN36-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5MN36-0BL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA2163-5MN36-0BL0 is a 3-pole molded case circuit breaker (MCCB) rated for a flat 63 A across the full operating temperature range from 40 °C to 70 °C — no derating curve to chase. That makes it a straight drop-in for motor branch circuits where the load current sits at 63 A and the ambient inside the panel runs warm. Its interrupting ratings climb to 187 kA at 240 V and hold at 121 kA through 415–440 V, then step down to 75.6 kA at 500 V and 3.7 kA at 690 V. That SCCR headroom at the lower voltages covers most industrial distribution panels without needing a current-limiting upstream device. This variant is explicitly designed for motor protection, with phase failure detection built in and an undervoltage release (UVR) factory-fitted. The auxiliary switch block carries two auxiliary switches plus one trip alarm and one electrical alarm switch — enough status feedback for a PLC input card without adding a separate interface relay.

Panel fit and integration

Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard SENTRON 3VA frame size that mounts on a DIN rail or panel-mount adapter. The 86 mm depth leaves clearance behind a 200 mm deep enclosure door with room for wiring gutters. Operating temperature spans -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power loss is 6.5 W, which keeps internal cabinet heating manageable even in a densely packed sub-panel.

Frequently asked questions

How do I get current pricing and availability for 3VA2163-5MN36-0BL0?

Submit an RFQ through this listing. The part is sourced to order; pricing and stock status are confirmed at quote time.

What is 3VA2163-5MN36-0BL0's interrupting capacity at 240 V?

187 kA at 240 V, stepping to 121 kA at 415–440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

Does this MCCB include an undervoltage release?

Yes, the design includes an undervoltage release (UVR) as the auxiliary release, plus phase failure detection.

What auxiliary switches come with 3VA2163-5MN36-0BL0?

Two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ configuration).

MPN