Siemens 3VA2163-5MN36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5MN36-0HC0 SENTRON MCCB, 63 A, 3-Pole, Motor

MPN3VA2163-5MN36-0HC0

Siemens SENTRON 3VA2163-5MN36-0HC0, molded case circuit breaker, 3-pole, 63 A, motor protection, ETU350M, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5MN36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2163-5MN36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2163-5MN36-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.75 W

Protection & Trip Unit

3VA2163-5MN36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2163-5MN36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5MN36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2163-5MN36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5MN36-0HC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

MCCB with ETU350M — 63 A, 3-pole, motor-protection curve

The Siemens 3VA2163-5MN36-0HC0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated at 63 A continuous current, built around the ETU350M electronic trip unit for motor protection. The ETU350M provides adjustable overload and short-circuit protection with phase-failure detection, so it's suited for protecting motor feeders where standard thermal-magnetic breakers might nuisance-trip on inrush. The 63 A rating holds flat from 40 °C to 50 °C; above that, it derates to 60.48 A at 55 °C and 56.7 A at 70 °C — factor that into panel ambient if you're pushing the thermal budget.

Breaking capacity across voltage levels

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. Those are high-interrupting ratings — the 121 kA at 415 V covers most industrial low-voltage fault levels without needing a current-limiting upstream fuse. The 17 kA at 690 V is still adequate for 690 V motor circuits in heavy industry, but verify your available fault current at that voltage level.

Panel integration and mounting

Dimensions are 105 mm wide, 181 mm high, 86 mm deep — fits standard SENTRON 3VA panel cutouts and busbar systems. The 86 mm depth is shallow enough for most 200 mm deep enclosures without crowding the gland plate. Latching endurance is 20,000 operations; the maximum power loss is 75 W, so account for that in thermal calculations if you're grouping several breakers. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

Where can I buy 3VA2163-5MN36-0HC0 and how do I get a price?

This part is available to order. Submit an RFQ through the storefront; availability and current pricing are confirmed at quote time. No stock count or price is published here.

What is the breaking capacity of 3VA2163-5MN36-0HC0 at 415 V?

121 kA at 415 V. The same rating applies at 440 V. At 240 V it is 187 kA, at 500 V it is 75.6 kA, and at 690 V it is 17 kA.

Does the 3VA2163-5MN36-0HC0 include a shunt trip?

Yes, it includes a shunt trip (STL) auxiliary release and two HQ auxiliary switches. No undervoltage release or communication function is fitted.

What is the rated continuous current of this MCCB at 60 °C?

59.22 A at 60 °C. The 63 A rating holds from 40 °C to 50 °C, then derates to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.

MPN
3VA2163-5MN36-0HC0