Skip to main content
Siemens 3VA2163-5MP36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5MP36-0AA0 SENTRON MCCB, 63 A, 121 kA at 415

MPN3VA2163-5MP36-0AA0
Active

Siemens SENTRON 3VA2163-5MP36-0AA0, molded case circuit breaker, 3-pole, 63 A, motor protection design, adjustable trip class 10A/10/10E/20/20E/30/30E, communication function, 121 kA at 415 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5MP36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2163-5MP36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classE
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-5MP36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-5MP36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5MP36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2163-5MP36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5MP36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Motor protection MCCB with communication

The Siemens SENTRON 3VA2163-5MP36-0AA0 is a 3-pole molded case circuit breaker (MCCB) designed specifically for motor protection, rated 63 A continuous current across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling. Breaking capacity hits 121 kA at 415 V and 187 kA at 240 V, with 75.6 kA at 500 V and 3.7 kA at 690 V — selectivity headroom for most distribution panels feeding motor control centers. Trip class is field-adjustable across 10A, 10/10E, 20/20E, and 30/30E.

Current production — no lifecycle risk

Standard SENTRON 3VA platform documentation (IEC/UL ratings, CE, UKCA, EAC) applies; the motor protection variant carries the same approvals as the base series.

Panel fit and mounting

Dimensions are 105 mm wide × 181 mm high × 86 mm deep — fits standard SENTRON 3VA panel cutouts and busbar systems; the 86 mm depth keeps it clear of shallow enclosure doors. Rated insulation voltage 800 V, power loss 4 W max at rated current — thermal budget inside the enclosure stays low for grouping multiple breakers.

Frequently asked questions

Does 3VA2163-5MP36-0AA0 have communication capability?

Yes, it includes a communication function for remote monitoring and trip indication.

What compliance documentation does Siemens provide for this MCCB?

Standard SENTRON 3VA documentation covers IEC/UL ratings, CE, UKCA, and EAC compliance for the motor protection variant.

MPN
3VA2163-5MP36-0AA0