Skip to main content
Siemens 3VA2163-6HL32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-6HL32-0AD0 SENTRON MCCB, 63 A, 242 kA

MPN3VA2163-6HL32-0AD0

Siemens SENTRON 3VA2, Molded case circuit breaker, 3VA2163-6HL32-0AD0, 3-pole, 63 A, 242 kA at 240 V, ETU320 trip unit, 3 auxiliary switches HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-6HL32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2163-6HL32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.4 W
3VA2163-6HL32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-6HL32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-6HL32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2163-6HL32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-6HL32-0AD0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

63 A MCCB with 242 kA interrupting capacity

The Siemens 3VA2163-6HL32-0AD0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current, with a breaking capacity of 242 kA at 240 V — that's the headline number, but what matters for panel design is the full voltage curve: 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V. Three auxiliary switches (HQ type) are built in, so you get status feedback without adding external contact blocks.

Panel fit and thermal derating

The breaker measures 105 mm wide × 181 mm tall × 86 mm deep — a standard 3-pole MCCB footprint that fits SENTRON 3VA2 mounting bases. Thermal derating is published: full 63 A up to 50 °C ambient, then it tapers to 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C.

Frequently asked questions

Where can I buy 3VA2163-6HL32-0AD0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send your quantity and target lead time for a competitive quote.

What is 3VA2163-6HL32-0AD0's breaking capacity at 415 V?

At 415 V the breaking capacity is 187 kA, same as at 440 V. At 240 V it's 242 kA, at 500 V it's 121 kA, and at 690 V it's 5 kA.

What trip unit does the 3VA2163-6HL32-0AD0 use?

It uses the ETU320 electronic trip unit, which provides adjustable overload and short-circuit protection. This is a basic version without communication, voltage trigger, or ground-fault monitoring.

Will 3VA2163-6HL32-0AD0 drop into a panel that was specified around 3VA1010-2ED42-0AE0 without rewiring?

No — the 3VA1010-2ED42-0AE0 is a different frame size (100 A frame, 10 A rating) with different mounting dimensions and bus-bar spacing. The 3VA2163 is a 160 A frame. Panel rework and bus reconfiguration would be required.

MPN
3VA2163-6HL32-0AD0