Skip to main content
Siemens 3VA2163-6HL32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-6HL32-0BA0 SENTRON MCCB, 63 A, 242 kA at 240

MPN3VA2163-6HL32-0BA0

Siemens SENTRON 3VA2163-6HL32-0BA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 242 kA breaking capacity at 240 V AC, undervoltage release, ETU320 trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-6HL32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-6HL32-0AA0
3VA2163-6HL32-0BA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.6.5 W
3VA2163-6HL32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-6HL32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-6HL32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-6HL32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-6HL32-0BA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Siemens 3VA2163-6HL32-0BA0 — 63 A MCCB with Undervoltage Release

The Siemens SENTRON 3VA2163-6HL32-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current at 40 °C, with a line-protection ETU320 trip unit. Its interrupting capacity reaches 242 kA at 240 V AC, 187 kA at 415 V, and 5 kA at 690 V — figures that govern selectivity and SCCR coordination in a distribution panel. No auxiliary contacts or communication module are fitted on this variant.

Above that, derating applies: 60.6375 A at 55 °C, 58.275 A at 60 °C, 55.9125 A at 65 °C, and 53.55 A at 70 °C.

Dimensions: 181 mm height, 105 mm width, 86 mm depth. The 3-pole footprint fits standard Siemens SENTRON mounting bases and busbar systems in distribution panels. The undervoltage release wiring terminates at the integrated trip block.

Frequently asked questions

What is the breaking capacity of 3VA2163-6HL32-0BA0 at 240 V?

242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V.

Where can I buy 3VA2163-6HL32-0BA0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation does Siemens provide for this MCCB?

Siemens SENTRON MCCBs typically carry UL, CSA, CE, and IEC certifications, with RoHS and REACH declarations available on request. Specific approvals for this variant should be confirmed at order.

MPN