Skip to main content
Siemens 3VA2163-6HL32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-6HL32-0DA0 SENTRON MCCB, 63 A, 242 kA

MPN3VA2163-6HL32-0DA0

Siemens SENTRON 3VA2163-6HL32-0DA0, molded case circuit breaker, 3-pole, 63 A rated continuous current Iu, ETU320 electronic trip unit, 242 kA breaking capacity at 240 V, undervoltage release, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-6HL32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-6HL32-0AA0
3VA2163-6HL32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.6.5 W
3VA2163-6HL32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-6HL32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-6HL32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-6HL32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-6HL32-0DA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens 3VA2163-6HL32-0DA0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current at 40 °C, with a 242 kA interrupting capacity at 240 V — that figure drops to 187 kA at 415 V and 121 kA at 500 V, so the SCCR you design to depends on your system voltage. The 63 A rating holds flat from 40 °C through 50 °C, then derates to 60.6 A at 55 °C and 53.5 A at 70 °C — so in a warm enclosure you lose about 15 % of capacity at the top end.

Dimensions are 105 mm wide × 181 mm high × 86 mm deep — the 105 mm width is a standard 3-pole MCCB footprint for the SENTRON 3VA2 frame, so it drops into existing panel cutouts and busbar systems designed for that frame.

Frequently asked questions

Where can I buy 3VA2163-6HL32-0DA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2163-6HL32-0DA0 at different voltages?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V. The rating drops significantly above 500 V, so verify system voltage against the curve before specifying.

What trip unit does the 3VA2163-6HL32-0DA0 use?

It uses an ETU320 electronic trip unit, configured for line protection. The undervoltage release (UVR) is integrated as standard.

Will 3VA2163-6HL32-0DA0 fit a panel designed for a 3VA1010-2ED32-0JA0?

The 3VA2163 is a larger frame (105 mm wide vs the 3VA1010's narrower 2-pole or smaller frame width) and higher current rating. It will not drop into the same cutout without panel modification — check the busbar and mounting hole pattern before substituting.

MPN
3VA2163-6HL32-0DA0