Skip to main content
Siemens 3VA2163-6HL36-0AB0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2163-6HL36-0AB0 MCCB, 63 A, 3-Pole, 242 kA at 240

MPN3VA2163-6HL36-0AB0

SENTRON 3VA2163-6HL36-0AB0, molded case circuit breaker, 3-pole, 63 A continuous, 95–756 A trip range, 242 kA breaking capacity at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-6HL36-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21636HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11

Ratings

3VA2163-6HL36-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-6HL36-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-6HL36-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-6HL36-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2163-6HL36-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-6HL36-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries — and what it doesn't

The SENTRON 3VA2163-6HL36-0AB0 is a 3-pole molded case circuit breaker rated 63 A continuous with an adjustable thermal-magnetic trip covering 95 A to 756 A. It's designed for line protection — not motor or generator protection — so the trip curve is shaped for feeder and distribution duty, not for starting inrush. Breaking capacity sits at 242 kA at 240 V, drops to 187 kA at 415 V and 440 V, then 121 kA at 500 V, and 3.7 kA at 690 V. That 242 kA at 240 V tells you it's built for high-fault panels — think transformer secondaries or busway feeds where the available fault current is stiff. No derating from 40 °C through 70 °C ambient — the full 63 A holds across that range. That's unusual for a molded case; most breakers start knocking current down above 40 °C. If your panel runs hot, this one doesn't force a upsizing.

Footprint and panel fit

Dimensions are 105 mm wide, 181 mm tall, 86 mm deep. That 105 mm width is the standard 3-pole MCCB footprint for this frame size — it drops into the same DIN-rail or panel-mount cutout as other SENTRON 3VA frame breakers. No surprise on the gland plate. Rated insulation voltage is 800 V. Power loss is 4 W maximum.

MPN