Skip to main content
Siemens 3VA2163-6HL36-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-6HL36-0AG0 SENTRON MCCB, 63 A, 3-Pole, 242 k

MPN3VA2163-6HL36-0AG0

Siemens SENTRON molded case circuit breaker, 3VA2163-6HL36-0AG0, line protection, 3-pole, 63 A rated continuous current, breaking capacity 242 kA at 240 VAC, 187 kA at 415/440 VAC, 121 kA at 500 VAC, 3.7 kA at 690 VAC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-6HL36-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21636HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2163-6HL36-0AG0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W
3VA2163-6HL36-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2163-6HL36-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-6HL36-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2163-6HL36-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-6HL36-0AG0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

SENTRON 3VA2 line protection MCCB — 63 A, 3-pole

Three-pole configuration, rated insulation voltage 800 V. Breaking capacity is the headline number here: 242 kA at 240 VAC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. The drop to 3.7 kA at 690 V is typical for this class; the 690 V rating governs the high-voltage end, not the common 400/480 V range where it still holds 187 kA.

Fit and mounting — panel integration

That gives you a remote status contact for the breaker position and a separate contact that changes state only on a trip event — useful for PLC-based alarm annunciation without extra wiring.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

242 kA at 240 VAC, 187 kA at 415 VAC and 440 VAC, 121 kA at 500 VAC, and 3.7 kA at 690 VAC. The 242 kA figure at 240 V is exceptionally high for a 63 A frame — this breaker handles high-fault installations.

What are the mounting dimensions for 3VA2163-6HL36-0AG0?

105 mm wide, 181 mm high, 86 mm deep. That 105 mm width matches the standard 3-pole SENTRON frame footprint for DIN-rail or direct-busbar mounting.

Does this breaker include auxiliary contacts?

Yes, it comes with one auxiliary switch and one trip alarm switch (HP type) pre-installed — no separate ordering needed for basic remote status and trip indication.

MPN
3VA2163-6HL36-0AG0