Skip to main content
Siemens 3VA2163-6HL36-0BH0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2163-6HL36-0BH0 63A MCCB, 3-Pole, 242kA at 240V

MPN3VA2163-6HL36-0BH0

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2163-6HL36-0BH0, 63 A, 3-pole, line protection, 242 kA at 240 V, with undervoltage release and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-6HL36-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21636HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2163-6HL36-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W
3VA2163-6HL36-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2163-6HL36-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-6HL36-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2163-6HL36-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-6HL36-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB with full-rated thermal performance

The Siemens SENTRON 3VA2163-6HL36-0BH0 is a 63 A, 3-pole molded case circuit breaker (MCCB) designed for line protection. Its continuous current rating holds flat at 63 A across the full operating temperature range from 40 °C to 70 °C — no derating curve to calculate, which simplifies panel sizing in warm enclosures. Breaking capacity reaches 242 kA at 240 V, drops to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. That 242 kA figure at 240 V covers high-fault utility feeds and transformer secondaries; the 187 kA at 415 V suits most European industrial distribution panels. The UVR drops the breaker on loss of control voltage — standard for emergency-stop circuits and safety isolation schemes.

Dimensions are 181 mm high, 105 mm wide, 86 mm deep. The 105 mm width is the standard 3-pole MCCB footprint for this SENTRON frame size — it occupies the same panel cutout as other 3VA2 breakers, so a panel laid out for a 3VA2116 variant accepts this unit without re-drilling the mounting plate or re-routing busbars. Power loss is rated at 6.5 W maximum.

Frequently asked questions

What auxiliary switches come on this variant?

Two auxiliary switches plus one trip alarm switch (HQ), factory-fitted. The undervoltage release (UVR) is also included.

MPN