Siemens 3VA2163-6HN32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-6HN32-0BH0 SENTRON MCCB, 63 A, 3-Pole, Line

MPN3VA2163-6HN32-0BH0

Siemens SENTRON 3VA2163-6HN32-0BH0, molded case circuit breaker, 3-pole, 63 A, line protection, ETU350 release, 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-6HN32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2163-6HN32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-6HN32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2163-6HN32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-6HN32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2163-6HN32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-6HN32-0BH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens SENTRON 3VA2163-6HN32-0BH0 is a 3-pole molded case circuit breaker (MCCB) rated for a continuous current Iu of 63 A, configured for line protection. It carries a breaking capacity of 242 kA at 240 V, stepping down to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V — the voltage-dependent curve you need for selectivity studies. The overcurrent release is an ETU350 electronic trip unit, and the breaker includes an undervoltage release (UVR) as the auxiliary release design. This is a current-production part, actively manufactured.

What the ratings mean for your panel

The 63 A rating holds flat from 40 °C through 50 °C ambient — no derating needed in a typical ventilated enclosure. At 55 °C it drops to 60.6 A, at 60 °C to 58.3 A, at 65 °C to 55.9 A, and at 70 °C to 53.6 A. If your panel runs hot, that thermal curve governs the actual continuous current the breaker can carry without nuisance tripping. The rated insulation voltage Ui of 800 V means the internal clearances and creepage are designed for 800 V phase-to-phase, so this MCCB is suitable for 690 V systems (the highest voltage where a breaking capacity is listed) without derating the insulation. The auxiliary contact version is 2 auxiliary switches plus 1 trip alarm switch (HQ type), giving you three separate signal paths — two for status feedback (open/closed) and one dedicated to trip indication. The trip indicator is also present on the front face for local visual confirmation. Maximum power loss is 6.5 W — low enough that heat buildup in a standard enclosure is negligible, but worth checking if you are grouping several breakers in a sealed, non-ventilated cabinet.

Physical fit and integration

Dimensions are 181 mm height, 105 mm width, 86 mm depth. The 105 mm width is the standard 3-pole MCCB footprint for the SENTRON 3VA platform — it mounts on a mounting plate or DIN rail via the appropriate adapter, and the front face accepts the standard rotary handle or motor operator. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The storage limit governs handling and warehousing, not running conditions.

Frequently asked questions

How do I get current pricing and availability for 3VA2163-6HN32-0BH0?

Submit an RFQ through this listing. The part is sourced through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2163-6HN32-0BH0 at 415 V?

187 kA at 415 V and at 440 V. At 240 V it is 242 kA, at 500 V it is 121 kA, and at 690 V it is 5 kA.

What type of overcurrent release does this MCCB use?

It uses an ETU350 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves.

Does 3VA2163-6HN32-0BH0 include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release design.

MPN
3VA2163-6HN32-0BH0