Skip to main content
Siemens 3VA2163-6HN32-0CH0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2163-6HN32-0CH0 MCCB, 63 A, 242 kA at 240 V

MPN3VA2163-6HN32-0CH0

SENTRON 3VA2163-6HN32-0CH0 molded case circuit breaker, 3-pole, 63 A, line protection, 242 kA interrupting at 240 V, ETU350 electronic trip unit, IP40 front, 86 x 105 x 181 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-6HN32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2163-6HN32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W
3VA2163-6HN32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2163-6HN32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-6HN32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2163-6HN32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-6HN32-0CH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Interrupting capacity and what it means for panel coordination

At 415 V it still holds 187 kA, and at 690 V it drops to 3.7 kA, which is typical for a 63 A frame at that voltage.

Thermal derating and ambient conditions

The ETU350 trip unit compensates digitally.

Lifecycle status is current. The undervoltage release is present. No communication function is built in.

MPN
3VA2163-6HN32-0CH0