At 415 V it still clears 187 kA, so it holds coordination downstream of a 2000 kVA transformer without cascading.
Breaking capacity and thermal performance
At 690 V the rating drops to 3.7 kA, so it is not a primary choice for 690 V distribution; that is a coordination note for anyone running a 690 V drive bus.
That covers remote trip, status feedback, and alarm annunciation without adding external relays. The shunt trip is wired separately from the main circuit — verify control voltage compatibility with the panel's 24 V DC or 110 V AC supply.
The 105 mm width is three pole spaces on a 35 mm grid — no extra width for the shunt trip or auxiliary switches, they tuck into the accessory compartment.