Siemens 3VA2163-6HN36-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-6HN36-0HA0 SENTRON MCCB, 63 A, 242 kA at 240

MPN3VA2163-6HN36-0HA0

Siemens SENTRON 3VA2163-6HN36-0HA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 242 kA interrupting capacity at 240 VAC, shunt trip release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-6HN36-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-6HN36-0AA0

Ratings

3VA2163-6HN36-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-6HN36-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-6HN36-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-6HN36-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2163-6HN36-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-6HN36-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

SENTRON 3VA2 MCCB, 63 A Frame, Shunt Trip

The Siemens 3VA2163-6HN36-0HA0 is a SENTRON molded case circuit breaker (MCCB) in a 3-pole configuration, rated for a continuous current of 63 A across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to the frame limit. It is designed for line protection, meaning it sits at the main distribution point or feeder branch to protect cables and busbars from overloads and short circuits. The interrupting capacity hits 242 kA at 240 VAC and still holds 187 kA at 415/440 VAC, which gives solid selectivity headroom in high-fault industrial panels. This variant ships with a shunt trip release (STL) as the auxiliary release, so it can be remotely tripped by a separate control signal — useful for emergency-stop circuits or remote disconnect schemes. There is no undervoltage release, no ground-fault monitoring, and no communication function; this is a straightforward line-protection breaker with remote trip capability. The supplied basic switch is order code 3VA2163-6HN36-0AA0, which is the base breaker without the shunt trip module.

Interrupting Capacity and Selectivity

At 240 VAC the breaker interrupts 242 kA symmetrical; at 415 V and 440 VAC it still manages 187 kA. That drops to 121 kA at 500 VAC and to 3.7 kA at 690 VAC. For a 63 A frame, these numbers mean the breaker can clear a bolted fault upstream without requiring a current-limiting fuse ahead of it — the SCCR of the panel it lives in is effectively limited by the bus bracing, not the breaker. The 3.7 kA at 690 V is the weak point; if your distribution runs at 690 V, verify the available fault current stays under that.

Dimensions and Panel Fit

The breaker footprint is 105 mm wide by 181 mm tall by 86 mm deep. That 86 mm depth is the overall body depth including the arc-chamber housing — it fits standard 200 mm deep distribution enclosures with room for wiring gutters. Width of 105 mm is a three-pole 63 A frame; it occupies three 35 mm DIN-rail module positions if using a DIN adapter, though the 3VA2 series typically bolts directly to a mounting plate in the panel.

Frequently asked questions

What is the interrupting capacity of this MCCB at 240 V?

The interrupting capacity is 242 kA at 240 VAC, 187 kA at 415/440 VAC, 121 kA at 500 VAC, and 3.7 kA at 690 VAC.

Does this breaker include a shunt trip?

Yes, the auxiliary release is a shunt trip (STL) for remote tripping. There is no undervoltage release and no ground-fault monitoring.

Where can I buy 3VA2163-6HN36-0HA0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA2163-6HN36-0HA0