Breaking capacity hits 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 3.7 kA at 690 V. The unit includes a factory-fitted shunt trip (STL) release and two HQ auxiliary switches, so it arrives ready for remote trip and status feedback without adding accessory modules. Max power loss is 4 W, which keeps panel heat rise manageable in a dense enclosure.
Integration notes
Wire range accepts conductors sized for 63 A continuous — typically 16–25 mm² copper depending on termination method and local code. The shunt trip (STL) operates on a separate control voltage; verify coil rating matches the control circuit before energizing.