Skip to main content
Siemens 3VA2163-6HN36-0HL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-6HN36-0HL0 SENTRON MCCB, 63 A, 3-Pole

MPN3VA2163-6HN36-0HL0

Siemens SENTRON 3VA2163-6HN36-0HL0, molded case circuit breaker, 3-pole, 63 A continuous, 242 kA breaking at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-6HN36-0HL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-6HN36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2163-6HN36-0HL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-6HN36-0HL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-6HN36-0HL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-6HN36-0HL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2163-6HN36-0HL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-6HN36-0HL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB with full-rated breaking capacity across the voltage range

The Siemens SENTRON 3VA2163-6HN36-0HL0 is a 3-pole molded case circuit breaker rated for 63 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed as the panel warms up. Breaking capacity runs 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 3.7 kA at 690 V, so the same unit handles high-fault commercial mains and lower-fault industrial feeds without a frame-size jump. Design is line protection, meaning the trip curve and accessories are set for feeder and main breaker duty rather than motor or generator protection. The auxiliary switch complement — 2 auxiliary switches plus a trip alarm and an electrical alarm switch — gives the panel builder status feedback without adding a separate interface relay.

Panel fit and mounting

Dimensions: 105 mm wide, 181 mm high, 86 mm deep. Three-pole footprint matches the SENTRON 3VA family cutout.

Auxiliary releases and accessories

Fitted with a shunt trip release (STL) for remote tripping. The auxiliary switch configuration — 2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ — provides separate dry contacts for status, trip indication, and remote annunciation. No undervoltage release and no ground-fault monitoring on this variant. Power loss is 4 W maximum, negligible for panel thermal budgeting. Operating temperature range -25 °C to 70 °C; storage range -40 °C to 80 °C.

MPN
3VA2163-6HN36-0HL0