Siemens 3VA2163-7HL36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7HL36-0AA0 SENTRON MCCB, 63 A, 330 kA at 240

MPN3VA2163-7HL36-0AA0
Active

Siemens SENTRON molded case circuit breaker, 3VA2163-7HL36-0AA0, 3-pole, 63 A, ETU320 electronic trip unit, 330 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-7HL36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2163-7HL36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.4 W
3VA2163-7HL36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-7HL36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-7HL36-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-7HL36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-7HL36-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

The Siemens SENTRON 3VA2163-7HL36-0AA0 is a 3-pole molded case circuit breaker rated 63 A continuous at 40 °C through 70 °C — no derating needed across that range, which simplifies panel calculations in warm enclosures. The ETU320 electronic trip unit gives adjustable short-time delay (tr min 0.5 s, tr max 17 s) for selective coordination downstream — critical on a main or feeder breaker where you want the branch to clear first.

Front IP40 protects against tool entry; the enclosure interior is not sealed. Optional motor drive available for remote operation.

Electrical ratings and selectivity headroom

The 690 V interrupting rating drops to 3.8 kA — that voltage level is outside this breaker's sweet spot; for 690 V applications a higher-rated frame is the better choice.

Frequently asked questions

What is the interrupting capacity of this MCCB?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.8 kA at 690 V.

Where can I buy 3VA2163-7HL36-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What trip unit does the 3VA2163-7HL36-0AA0 use?

It uses the ETU320 electronic overcurrent release with adjustable short-time delay from 0.5 s to 17 s.

MPN
3VA2163-7HL36-0AA0