Skip to main content
Siemens 3VA2163-7HN32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7HN32-0AB0 SENTRON MCCB, 63 A, 3-Pole, ETU35

MPN3VA2163-7HN32-0AB0

Siemens SENTRON 3VA2163-7HN32-0AB0, molded case circuit breaker, 3-pole, 63 A, ETU350 electronic trip unit, 330 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-7HN32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-7HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA2163-7HN32-0AB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V5.25 kA
Power loss, max.4 W
3VA2163-7HN32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2163-7HN32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-7HN32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2163-7HN32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-7HN32-0AB0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens 3VA2163-7HN32-0AB0 is a 3-pole SENTRON molded case circuit breaker rated for line protection, with a continuous current Iu of 63 A at 40 °C, 45 °C, and 50 °C — meaning it holds full 63 A without derating through 50 °C ambient. The interrupting ratings are high: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 5.25 kA at 690 V. That 330 kA at 240 V covers most low-voltage fault scenarios in industrial distribution, so it can be placed upstream without worrying about cascading failure. The front face is IP40, so it's fine in a dry panel but not washdown-rated.

That 105 mm width is the standard 3-pole MCCB footprint for the SENTRON 3VA2 frame — it drops into the same panel cutout and bus-bar spacing as other 3VA2 3-pole units. The 86 mm depth means it clears most standard enclosure depths, but check your back-panel clearance if you're retrofitting into a shallow box.

Frequently asked questions

What is the interrupting rating at 415 V?

242 kA at 415 V, and the same at 440 V. At 500 V it drops to 187 kA, and at 690 V to 5.25 kA.

Where can I buy 3VA2163-7HN32-0AB0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA2163-7HN32-0AB0 drop into a panel designed for 3VA1010-2ED32-0JA0?

The 3VA2163-7HN32-0AB0 is a 3-pole 63 A MCCB with an ETU350 electronic trip unit, while the 3VA1010-2ED32-0JA0 is a different frame size and rating. The physical footprint (105 mm width, 181 mm height, 86 mm depth) is specific to the 3VA2 frame; the 3VA1010 belongs to a smaller frame. Panel cutouts and bus-bar spacing differ — verify mechanical fit before ordering.

What compliance documentation is available for this MCCB?

The SENTRON series carries UL, CSA, and IEC certifications typical for industrial MCCBs. Specific documentation (RoHS, REACH, UL file number) is available on request at quote time.

MPN