Skip to main content
Siemens 3VA2163-7HN32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7HN32-0DA0 SENTRON MCCB, 63 A, 3-Pole, 330 k

MPN3VA2163-7HN32-0DA0

Siemens SENTRON 3VA2163-7HN32-0DA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 330 kA breaking capacity at 240 V AC, undervoltage release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-7HN32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-7HN32-0AA0
3VA2163-7HN32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W
3VA2163-7HN32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2163-7HN32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-7HN32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-7HN32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-7HN32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2163-7HN32-0DA0 — 63 A SENTRON MCCB with Undervoltage Release

Its interrupting capacity reaches 330 kA at 240 V AC, dropping to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — the 690 V figure is the one to watch when specifying for higher-voltage industrial feeds. The breaker carries an integrated undervoltage release (UVR), so it trips immediately if supply voltage drops below the release threshold — a common requirement for safety circuits and motor feeder disconnects.

The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — the 105 mm width is the critical dimension for multi-pole grouping in a distribution board, matching the standard SENTRON 3VA2 footprint.

Environmental & Compliance — Wide Operating Range

Frequently asked questions

Will 3VA2163-7HN32-0DA0 drop into a panel specified around 3VA2163-8HM32-0AA0 without rewiring?

Yes — both share the same 105 mm width, 181 mm height, and 86 mm depth, so the mechanical footprint is identical. The electrical difference is the undervoltage release on the -7HN32-0DA0; if the panel wiring already includes the UVR coil circuit, it's a direct swap. If not, the UVR terminals simply go unused.

MPN
3VA2163-7HN32-0DA0