Skip to main content
Siemens 3VA2163-7HN32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7HN32-0JC0 SENTRON MCCB, 63 A, 3-Pole, 330 k

MPN3VA2163-7HN32-0JC0

Siemens SENTRON 3VA2163-7HN32-0JC0, 3-pole molded case circuit breaker, 63 A continuous, 330 kA interrupting at 240 V, with shunt trip and 2 auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-7HN32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-7HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2163-7HN32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W
3VA2163-7HN32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2163-7HN32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-7HN32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2163-7HN32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-7HN32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this 3VA2163-7HN32-0JC0 brings to the panel

The Siemens SENTRON 3VA2163-7HN32-0JC0 is a 3-pole molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which matters when the breaker sits in a warm cabinet next to other heat sources. Its interrupting capacity hits 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 3.7 kA at 690 V — numbers that put it squarely in the high-fault category for industrial distribution where available short-circuit current is substantial.

At 105 mm wide, 181 mm tall, and 86 mm deep, this 3-pole MCCB fits the standard SENTRON 3VA2 panel cutout — the same footprint as other 63 A frames in the series, so a swap from a different 3VA2 variant means no re-drilling or busbar rework. The base switch is 3VA2163-7HN32-0AA0; the -0JC0 suffix adds the shunt trip and auxiliary switches at the factory, saving a wiring step on the panel build.

Frequently asked questions

What auxiliary components come built in?

Two auxiliary switches (HQ design) and a shunt trip (STL) release are factory-installed, so the breaker arrives ready for remote trip and status indication without separate add-on modules.

MPN
3VA2163-7HN32-0JC0