Skip to main content
Siemens 3VA2163-7MN32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7MN32-0BH0 SENTRON MCCB, 63 A, 3-Pole, 330 k

MPN3VA2163-7MN32-0BH0

Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2163-7MN32-0BH0, 63 A at 40 °C, 3-pole, 330 kA breaking capacity at 240 V, motor protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-7MN32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-7MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2163-7MN32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-7MN32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-7MN32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-7MN32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2163-7MN32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-7MN32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

SENTRON 3VA2 MCCB for Motor Protection

The Siemens 3VA2163-7MN32-0BH0 is a SENTRON 3VA2 series molded case circuit breaker (MCCB) rated for 63 A continuously at 40 °C, with no derating needed up to 70 °C — it holds 63 A across the full ambient range. That flat thermal curve simplifies panel design in warm enclosures where other breakers would force a downsized main. Three-pole construction with a motor-protection trip characteristic. Phase failure detection is built in — the breaker trips on loss of a phase, preventing single-phasing damage on a motor load. An undervoltage release (UVR) is factory-fitted, allowing remote or safety-circuit dropout.

Breaking Capacity — Where It Matters

Breaking capacity is 330 kA at 240 V AC, dropping to 242 kA at 415 V and 440 V, then 187 kA at 500 V. At 690 V it still clears 3.7 kA. For a 63 A frame, that 330 kA at 240 V means it handles high-fault conditions typical on large secondary substations or near transformer secondaries — not just branch-circuit faults. The 242 kA at 415 V covers most European industrial distribution panels.

Panel Fit and Auxiliary Wiring

Dimensions: 105 mm wide, 181 mm tall, 86 mm deep. The 105 mm width is three 35 mm DIN spaces — standard for a 3-pole MCCB in this class. Mounts on DIN rail or panel-mount via the 3VA2 base. Auxiliary switch complement: two auxiliary switches plus one trip alarm switch (HQ type), pre-wired from the factory. The basic switch assembly is order code 3VA2163-7MN32-0AA0 if you need a replacement contact block.

Frequently asked questions

What is the breaking capacity of 3VA2163-7MN32-0BH0 at 415 V?

242 kA at 415 V AC, which covers most industrial distribution panel fault levels.

Does 3VA2163-7MN32-0BH0 include phase failure protection?

Yes, phase failure detection is built in — the breaker trips on loss of a phase to prevent motor damage from single-phasing.

What is the width of 3VA2163-7MN32-0BH0 in inches?

4.13 inches (105 mm), which is three standard 35 mm DIN-rail spaces.

Where can I buy 3VA2163-7MN32-0BH0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
3VA2163-7MN32-0BH0