Siemens 3VA2163-7MN36-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7MN36-0BL0 SENTRON MCCB, 63 A, 3-Pole, Motor

MPN3VA2163-7MN36-0BL0

Siemens SENTRON 3VA2163-7MN36-0BL0, molded case circuit breaker, 3-pole, 63 A, motor protection variant with ETU350M electronic trip unit, 330 kA breaking capacity at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-7MN36-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2163-7MN36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2163-7MN36-0BL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-7MN36-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout

Construction & Connection

3VA2163-7MN36-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-7MN36-0BL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2163-7MN36-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-7MN36-0BL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Motor Protection MCCB with Flat Derating to 70 °C

The Siemens SENTRON 3VA2163-7MN36-0BL0 is a 3-pole molded case circuit breaker (MCCB) rated at 63 A continuous current, specifically configured as the motor protection variant. It carries the ETU350M electronic trip unit, which provides adjustable overload and short-circuit protection curves matched to motor starting characteristics. The breaker maintains its full 63 A rating across the entire operating temperature range from 40 °C through 70 °C — no derating needed up to the maximum ambient of 70 °C, which simplifies panel sizing in warm enclosures. Breaking capacity is substantial: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. That 330 kA figure at 240 V covers high-fault scenarios common in industrial distribution — useful when this breaker sits downstream of a large transformer or in a switchboard with high available fault current.

Panel Fit and Auxiliary Contact Configuration

Footprint: 105 mm wide, 181 mm tall, 86 mm deep. The 105 mm width is standard for a 3-pole 63 A frame in the 3VA series — it occupies three 35 mm DIN module positions if panel-mounted, or bolts directly into a mounting plate. Depth of 86 mm leaves clearance behind the panel for wiring and the auxiliary contact block. Comes equipped with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ configuration). That gives four signal outputs for status feedback to a PLC or annunciator — enough to cover open/closed, trip, and a separate electrical alarm without adding an external relay.

Protection and Release Features

Includes an undervoltage release and phase failure detection as standard — both critical for motor protection applications where a phase loss can single-phase a motor and cause winding damage. The undervoltage release trips the breaker when supply voltage drops below a threshold, preventing automatic restart after a dip. No ground-fault monitoring on this variant, and no communication function; it's a standalone protection device. Rated insulation voltage (Ui) is 800 V, which covers 690 V systems with margin. Power loss at rated current is 6.5 W maximum — modest for a 63 A MCCB, so ventilation requirements in the enclosure are minimal.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V.

Does this breaker require derating at high ambient temperatures?

No — it maintains its full 63 A rating from 40 °C through 70 °C, so no derating is needed up to the maximum operating ambient of 70 °C.

Where can I buy 3VA2163-7MN36-0BL0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2163-7MN36-0BL0