Skip to main content
Siemens 3VA2163-7MS32-0HL0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2163-7MS32-0HL0 MCCB, 63 A, 189-945 A tri

MPN3VA2163-7MS32-0HL0

Siemens SENTRON 3VA2163-7MS32-0HL0, 3-pole molded case circuit breaker, 63 A continuous, adjustable thermal-magnetic trip 189-945 A, 330 kA at 240 V, shunt trip, auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-7MS32-0HL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-7MS32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2163-7MS32-0HL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-7MS32-0HL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-7MS32-0HL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-7MS32-0HL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2163-7MS32-0HL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-7MS32-0HL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2163-7MS32-0HL0 — 63 A MCCB with 330 kA interrupting capacity

The Siemens SENTRON 3VA2163-7MS32-0HL0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current across the full ambient range of 40 °C to 70 °C — no derating needed up to that ceiling. Its adjustable thermal-magnetic trip unit covers 189 A to 945 A, so it's sized for motor or feeder protection where the load current lands well below the breaker's frame rating. This MCCB is designed for starter protection (per), meaning it's built to handle motor inrush and coordinate with a contactor and overload relay in a typical motor branch circuit. The interrupting ratings are substantial: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — so it can sit upstream of a high-fault panel without cascading failure.

Physical fit and auxiliary configuration

The 3VA2163-7MS32-0HL0 measures 105 mm wide, 181 mm tall, and 86 mm deep (4.13 × 7.13 × 3.39 inches). That 105 mm width is a standard 3-pole MCCB footprint for this frame size — verify the back-panel mounting hole pattern against your existing SENTRON or competitor cutout before committing the panel layout. Factory-fitted auxiliary switching includes two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ type). A shunt trip release (STL) is also installed. The breaker includes a trip indicator and a voltage trigger, but no undervoltage release, no ground-fault monitoring, and no communication module.

Frequently asked questions

Where can I buy 3VA2163-7MS32-0HL0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key interrupting ratings for this MCCB?

The 3VA2163-7MS32-0HL0 delivers 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — sufficient for high-fault-capacity service entrance or distribution panels.

What is the continuous current rating and trip range?

Continuous rating is 63 A from 40 °C to 70 °C ambient with no derating. The adjustable thermal-magnetic trip unit covers 189 A to 945 A — set the trip to match the load, not the frame.

What auxiliary switches and releases are fitted?

Factory-fitted: two auxiliary switches, one trip alarm switch, one electrical alarm switch (HQ), and a shunt trip release (STL). No undervoltage release, no ground-fault module, no communication.

MPN
3VA2163-7MS32-0HL0