Interrupting ratings and selectivity
The 3VA2163-7MS36-0AJ0: At 240 V the breaker clears 330 kA; at 415 V and 440 V it still handles 242 kA, dropping to 187 kA at 500 V and 3.7 kA at 690 V. That steep roll-off above 500 V means the 690 V rating is effectively a low-fault backup — plan coordination downstream of a current-limiting fuse if the service voltage runs above 500 V.
Thermal performance and panel fit
Power dissipation maxes at 4 W, so heat load inside a sealed cabinet is minimal.