Skip to main content
Siemens 3VA2163-7MS36-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7MS36-0CA0 SENTRON MCCB, 63 A, 3-Pole, UVR

MPN3VA2163-7MS36-0CA0

Siemens SENTRON 3VA2163-7MS36-0CA0, molded case circuit breaker, 3-pole, 63 A, 330 kA at 240 V, undervoltage release, active production.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-7MS36-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-7MS36-0AA0

Ratings

3VA2163-7MS36-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-7MS36-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-7MS36-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-7MS36-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2163-7MS36-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-7MS36-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries

The Siemens SENTRON 3VA2163-7MS36-0CA0 is a 3-pole molded case circuit breaker rated for 63 A continuous at 40 °C through 70 °C — no derating needed across that band, which simplifies panel sizing in warm enclosures. Its interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V, and still holds 187 kA at 500 V, dropping to 3.7 kA at 690 V. That 330 kA figure at 240 V tells you this breaker is built for high-fault utility or transformer-fed service entrances where available short-circuit current is extreme.

Undervoltage release and protection design

This variant ships with an undervoltage release (UVR) fitted — the auxiliary release is listed as undervoltage release. That means the breaker trips automatically when supply voltage drops below a threshold, protecting downstream loads from brownout conditions or preventing automatic reclosure after a dip. The design is starter protection, so it's intended for motor branch circuits where loss-of-voltage protection is part of the safety sequence. No auxiliary switch, no ground-fault monitoring, no communication function on this order code.

Panel fit and environmental limits

Footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard SENTRON 3VA frame size for this rating. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Maximum power loss is 6.5 W, manageable in a typical IP54 steel enclosure without forced ventilation. No trip indicator, no voltage trigger, no phase failure detection on this variant.

Frequently asked questions

Where can I buy 3VA2163-7MS36-0CA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not from a static listing.

What is the interrupting capacity of 3VA2163-7MS36-0CA0 at different voltages?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. The 330 kA rating at 240 V makes it suitable for high-fault service entrances.

What does the undervoltage release on this MCCB do?

The undervoltage release (UVR) trips the breaker when supply voltage drops below a set threshold, protecting downstream equipment from brownout conditions and preventing automatic reclosure after a dip. This variant is factory-fitted with the UVR.

MPN
3VA2163-7MS36-0CA0