Skip to main content
Siemens 3VA2163-7MS36-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7MS36-0CH0 SENTRON MCCB, 63 A, 3-Pole, Start

MPN3VA2163-7MS36-0CH0

Siemens SENTRON 3VA2163-7MS36-0CH0, molded case circuit breaker, 3-pole, 63 A, starter protection variant, ETU310M electronic trip unit, with undervoltage release and HQ auxiliary switch pack.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-7MS36-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Basic switch (supplied) ref.3VA2163-7MS36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2163-7MS36-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.75 W

Protection & Trip Unit

3VA2163-7MS36-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M

Construction & Connection

3VA2163-7MS36-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-7MS36-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2163-7MS36-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-7MS36-0CH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this 3VA2 is — and what it isn't

The 3VA2163-7MS36-0CH0 is a SENTRON molded case circuit breaker (MCCB) in the starter protection variant — meaning it's built for motor branch circuits where you need coordinated overload and short-circuit protection in one package, not just a straight feeder breaker. Rated continuous current Iu is 63 A, and it holds that rating from 40 °C up through 50 °C without derating; at 55 °C it's still at 60.48 A, and at 70 °C it's 56.7 A, so the thermal headroom is generous for a 63 A frame. The ETU310M electronic trip unit handles the overcurrent release, and there's an undervoltage release (UVR) integrated — the auxiliary release design is UVR, and the supplied basic switch is order code 3VA2163-7MS36-0AA0 with an integrated auxiliary trip of 3VA9608-0BB24. This is a 3-pole unit with a trip indicator, 2 auxiliary switches plus 1 trip alarm switch (HQ configuration). No communication function, no phase failure detection, no ground fault monitoring — this is a straightforward motor-protection MCCB, not a networked power monitor.

SCCR — what the interrupting ratings mean for panel coordination

The interrupting capacity is given across five voltage points, which is what you need for selectivity studies. At 240 V it's 330 kA; at 415 V and 440 V it's 242 kA; at 500 V it's 187 kA; at 690 V it's 52.5 kA. That 52.5 kA at 690 V is the limiting figure for most industrial installations — if your available fault current at the panel exceeds that, you need upstream current-limiting fuses or a higher-rated frame. The rated insulation voltage Ui is 800 V, so the breaker itself is insulated for 800 V systems, but the interrupting rating at that voltage is what governs the SCCR of the combination. Maximum power loss is 75 W — relevant for enclosure thermal calculations if you're packing multiple breakers in a sealed panel.

Panel fit — dimensions and integration

Footprint is 105 mm wide by 181 mm tall by 86 mm deep. That's a standard 3-pole MCCB form factor for the 3VA2 frame — it mounts on a DIN rail or directly to a backplate via the screw terminals. The 86 mm depth is the body only; allow additional clearance for the auxiliary switch wiring and the UVR coil connections. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Mechanical endurance is 20,000 operations — adequate for motor starting duty where the breaker isn't cycled daily as a disconnect.

Frequently asked questions

How do I get current pricing and availability for 3VA2163-7MS36-0CH0?

We source this part to order against an RFQ. Submit a request and we'll confirm current pricing and lead time at quote time.

Will 3VA2163-7MS36-0CH0 drop into a panel specified around 3VA2163-8HM32-0AA0?

The physical footprint is the same 3VA2 frame, so it will mount in the same DIN rail or backplate position. However, verify the auxiliary contact wiring (2 aux + 1 trip alarm vs the 8HM32's configuration) and the presence of the undervoltage release — the UVR coil wiring is additional and may require a different terminal assignment.

MPN
3VA2163-7MS36-0CH0