Skip to main content
Siemens 3VA2163-7MS36-0HL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7MS36-0HL0 SENTRON MCCB, 63 A, 3-Pole, 330 k

MPN3VA2163-7MS36-0HL0

Siemens SENTRON 3VA2163-7MS36-0HL0, molded case circuit breaker, 3-pole, 63 A rated current at 40 °C, breaking capacity 330 kA at 240 V, starter protection design with shunt trip and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-7MS36-0HL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2163-7MS36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2163-7MS36-0HL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W
3VA2163-7MS36-0HL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2163-7MS36-0HL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-7MS36-0HL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2163-7MS36-0HL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-7MS36-0HL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB for motor and starter protection

Rated 63 A continuously from 40 °C up to 70 °C, it holds its full ampacity across the typical panel ambient range without derating. Three poles, with a breaking capacity of 330 kA at 240 V and 242 kA at 415 V, so it safely interrupts high-fault currents in industrial low-voltage switchgear without cascading upstream. At 690 V the breaking capacity drops to 3.7 kA — still adequate for most 690 V motor circuits where the supply transformer limits fault current, but worth verifying against the site's available fault level if used on a 690 V bus.

Footprint: 105 mm wide × 181 mm tall × 86 mm deep. Fits standard 3-pole MCCB cutouts and busbar risers without adapter plates.

Frequently asked questions

What auxiliary switches and releases come with this breaker?

It includes a shunt trip (STL) release, two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ configuration).

MPN
3VA2163-7MS36-0HL0