Skip to main content
Siemens 3VA2163-7MS36-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7MS36-0KC0 SENTRON MCCB, 63 A, 3-Pole, 330 k

MPN3VA2163-7MS36-0KC0

Siemens SENTRON 3VA2163-7MS36-0KC0, molded case circuit breaker (MCCB), 3-pole, 63 A rated continuous current Iu, 330 kA interrupting capacity at 240 V, ETU310M electronic trip unit, starter protection version, with shunt trip and 2 HQ auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-7MS36-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Basic switch (supplied) ref.3VA2163-7MS36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2163-7MS36-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.75 W

Protection & Trip Unit

3VA2163-7MS36-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M

Construction & Connection

3VA2163-7MS36-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-7MS36-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2163-7MS36-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-7MS36-0KC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

63 A MCCB with 330 kA interrupting — what the ratings mean for your panel

The Siemens 3VA2163-7MS36-0KC0 is a SENTRON molded case circuit breaker (MCCB) in a starter protection version, rated for 63 A continuous current (Iu) with a 3-pole configuration. The ETU310M electronic overcurrent release provides adjustable protection curves, and the breaker carries a latching endurance of 20,000 operations. The shunt trip (STL) release and two HQ auxiliary switches are integrated.

Panel fit and integration

Dimensions are 105 mm wide, 181 mm high, and 86 mm deep. It mounts on a DIN rail or directly to a backplate in the standard SENTRON 3VA footprint. The 86 mm depth is shallow enough to fit a 200 mm deep enclosure with room for wiring gutters. The 75 W maximum power loss means you need to account for heat dissipation in a sealed cabinet — plan for ventilation or derating if the ambient inside the panel exceeds 50 °C. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C. The continuous current rating holds at 63 A up to 50 °C ambient; above that it derates to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. If your panel runs hot, the effective ampacity drops — size your load accordingly.

Frequently asked questions

Does this MCCB include a shunt trip or auxiliary contacts?

Yes, it includes a shunt trip (STL) release and two HQ auxiliary switches. It does not include an undervoltage release or ground-fault monitoring.

MPN