Skip to main content
Siemens 3VA2163-7MS36-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-7MS36-0KC0 SENTRON MCCB, 63 A, 3-Pole, 330 k

MPN3VA2163-7MS36-0KC0

Siemens SENTRON 3VA2163-7MS36-0KC0, molded case circuit breaker (MCCB), 3-pole, 63 A rated continuous current Iu, 330 kA interrupting capacity at 240 V, ETU310M electronic trip unit, starter protection version, with shunt trip and 2 HQ auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-7MS36-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Basic switch (supplied) ref.3VA2163-7MS36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2163-7MS36-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.75 W
3VA2163-7MS36-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
3VA2163-7MS36-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-7MS36-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2163-7MS36-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-7MS36-0KC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The ETU310M electronic overcurrent release provides adjustable protection curves, and the breaker carries a latching endurance of 20,000 operations.

The 75 W maximum power loss means you need to account for heat dissipation in a sealed cabinet — plan for ventilation or derating if the ambient inside the panel exceeds 50 °C. The continuous current rating holds at 63 A up to 50 °C ambient; above that it derates to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. If your panel runs hot, the effective ampacity drops — size your load accordingly.

Frequently asked questions

Does this MCCB include a shunt trip or auxiliary contacts?

Yes, it includes a shunt trip (STL) release and two HQ auxiliary switches. It does not include an undervoltage release or ground-fault monitoring.

MPN