Skip to main content
Siemens 3VA2163-8HK36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-8HK36-0AA0 SENTRON MCCB, 63 A, 3-Pole, ETU34

MPN3VA2163-8HK36-0AA0
Active

Siemens SENTRON 3VA2163-8HK36-0AA0, molded case circuit breaker, 3-pole, 63 A, ETU340 electronic trip unit, line protection version, breaking capacity 440 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-8HK36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2163-8HK36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.3.1 W
3VA2163-8HK36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
Overcurrent protection functionELISA LI
Ground-fault monitoringWithout
3VA2163-8HK36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-8HK36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-8HK36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-8HK36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2163-8HK36-0AA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel sizing in warm enclosures. Breaking capacity is rated 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — these are the maximum fault currents the breaker can safely interrupt at each voltage level, giving you the SCCR headroom for high-fault installations.

The 3VA2 frame accepts optional motor drive (listed as an optional extension), which can be specified for remote trip or reclose applications.

Frequently asked questions

Will 3VA2163-8HK36-0AA0 drop into a panel specified for 3VA1110-5ED36-0AA0 without rewiring?

The 3VA2163-8HK36-0AA0 is a 3-pole, 63 A MCCB on the 3VA2 frame with ETU340 trip unit, while the 3VA1110-5ED36-0AA0 is a different frame and rating. Panel cutout dimensions and busbar spacing must be verified against the 105 mm width, 181 mm height, and 86 mm depth before assuming interchangeability.

MPN
3VA2163-8HK36-0AA0