Skip to main content
Siemens 3VA2163-8JP46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-8JP46-0AA0 SENTRON MCCB, 63 A, 440 kA at 240

MPN3VA2163-8JP46-0AA0
Active

Siemens SENTRON 3VA2163-8JP46-0AA0, molded case circuit breaker, 4-pole, 63 A, ETU550 electronic trip unit, breaking capacity 440 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-8JP46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2163-8JP46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.3.1 W

Protection & Trip Unit

3VA2163-8JP46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-8JP46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-8JP46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2163-8JP46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-8JP46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What this MCCB delivers in the panel

The Siemens SENTRON 3VA2163-8JP46-0AA0 is a 4-pole molded case circuit breaker rated for 63 A continuous current with no derating across its full operating range up to 70 °C — the same 63 A holds from 40 °C through 70 °C, so you don't lose headroom in a warm enclosure. Its ETU550 electronic trip unit provides adjustable overload and short-circuit protection, with a minimum setting of 95 A and a maximum of 756 A, covering a wide range of feeder and branch circuit needs. Breaking capacity is 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — high enough for most industrial distribution panels with high fault-current potential, and it carries an 800 V rated insulation voltage.

Integration and mounting

The 3VA2163-8JP46-0AA0 measures 140 mm wide, 181 mm high, and 86 mm deep — fits standard panel-mount cutouts for 4-pole MCCBs in the 63 A frame class. Front IP40 protection keeps dust out of the trip-unit interface. A communication function is built in, supporting integration with higher-level monitoring or control systems — no separate comm module required for basic connectivity.

Frequently asked questions

What is the breaking capacity of 3VA2163-8JP46-0AA0 at 415 V?

Breaking capacity is 330 kA at 415 V, with the same rating at 440 V. At 240 V it reaches 440 kA, at 500 V it is 220 kA, and at 690 V it is 52.5 kA.

Where can I buy 3VA2163-8JP46-0AA0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request for a firm quote.

Does this MCCB include a communication function?

Yes, a communication function is built in, enabling integration with monitoring or control systems without an external module.

MPN