Skip to main content
Siemens 3VA2216-5HK42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2216-5HK42-0AA0 SENTRON MCCB, 160 A, 4-Pole, ETU3

MPN3VA2216-5HK42-0AA0
Active

Siemens SENTRON 3VA2 series, molded case circuit breaker, 160 A, 4-pole, ETU340 electronic trip unit, line protection design, breaking capacity 187 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2216-5HK42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2216-5HK42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.19.7 W
3VA2216-5HK42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
Overcurrent protection functionELISA LI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2216-5HK42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2216-5HK42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2216-5HK42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2216-5HK42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

Four poles, line-protection design, with an ETU340 electronic overcurrent release. Breaking capacity hits 187 kA at 240 V, drops to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 4.5 kA at 690 V. That's a lot of fault-clearing headroom for a 160 A frame — sized for high-available-fault-current panels where a standard MCCB would weld closed. The ETU340 release is a programmable electronic trip unit — not a fixed thermal-magnetic. That means you can dial in the long-time, short-time, instantaneous, and ground-fault (if equipped — this variant is without ground-fault monitoring) thresholds to coordinate with downstream feeders. Power loss sits at 19.7 W maximum, which matters for enclosed panel heat buildup.

That's a standard 4-pole MCCB footprint — it'll drop into a SENTRON 3VA2 mounting base or direct-panel mount without surprises. If you need shunt trip or aux contacts, those are add-on accessories that clip onto the 3VA2 frame, not built in.

The 3VA2116-5JP32-0AE0 is a 3-pole variant of the same 160 A frame. The 3VA2216-5HK42-0AA0 adds a fourth pole — that's the difference. Same ETU340 release family, same breaking capacity curve, same dimensions except the width (4-pole is wider). If your panel was wired for a 3-pole and you need 4-pole, this won't drop in without a busbar rework. If you're replacing a 4-pole, this is the direct fit.

MPN
3VA2216-5HK42-0AA0