Skip to main content
Siemens 3VA2216-5HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2216-5HL42-0AA0 MCCB, 160 A, 4-Pole, ETU3

MPN3VA2216-5HL42-0AA0
Active

Siemens SENTRON 3VA2216-5HL42-0AA0, molded case circuit breaker, 4-pole, 160 A continuous, ETU320 electronic trip unit, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2216-5HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2216-5HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.19.7 W

Protection & Trip Unit

3VA2216-5HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2216-5HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2216-5HL42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2216-5HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2216-5HL42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What this 160 A MCCB delivers

The Siemens SENTRON 3VA2216-5HL42-0AA0 is a 4-pole molded case circuit breaker rated for 160 A continuous current, carrying that rating flat from 40 °C through 70 °C ambient — no derating curve to chase in a warm enclosure. The ETU320 electronic trip unit gives you an adjustable overload pickup from 240 A up to 1,920 A, so one breaker body covers a wide range of downstream protection settings. Insulation voltage is rated 800 V, and the interrupting capacity hits 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V — a steep SCCR curve that matters when you're coordinating with upstream gear. Maximum power loss is 19.7 W.

Sourcing and lifecycle posture

Lifecycle stage is listed as current — no phase-out notice, no last-time-buy window. This is a standard catalog item from the SENTRON family. No undervoltage release, no communication function, no ground-fault monitoring version on this variant; it's a straight thermal-magnetic replacement with electronic trip adjustment. For a BOM freeze or a panel that needs a second-source gate, the closest functional peer is the 5SQ2670-2YA06 series — same frame size and trip range, but verify the terminal arrangement and accessory compatibility before swapping. We source this breaker to order against an RFQ; availability and current pricing are confirmed at quote time.

Frequently asked questions

Where can I buy 3VA2216-5HL42-0AA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request with your quantity and target delivery window; availability and current pricing are confirmed at quote time.

What is 3VA2216-5HL42-0AA0's interrupting capacity at 415 V?

The interrupting capacity is 121 kA at 415 V, and the same at 440 V. At 240 V it reaches 187 kA; at 500 V it drops to 75.6 kA; at 690 V it is 4.5 kA.

What trip unit does this MCCB use?

It uses the ETU320 electronic trip unit, with an adjustable overload pickup range from 240 A to 1,920 A.

Will 3VA2216-5HL42-0AA0 drop into a panel specified around 5SQ2670-2YA06 without rewiring?

The 5SQ2670-2YA06 series shares the same frame size and trip range, making it the closest functional peer. However, terminal arrangement and accessory compatibility should be verified before direct substitution — the mounting footprint is the same, but accessory slots and wiring lug positions may differ.

MPN