Siemens 3VA2216-5MN32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2216-5MN32-0HH0 MCCB, 160 A, 3-Pole, Moto

MPN3VA2216-5MN32-0HH0

Siemens SENTRON 3VA2216-5MN32-0HH0, molded case circuit breaker, 3-pole, motor protection design, rated 160 A at 40 °C, breaking capacity 121 kA at 415 V, 86 mm depth, 105 mm width, 181 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2216-5MN32-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2216-5MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2216-5MN32-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.19.7 W
3VA2216-5MN32-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2216-5MN32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2216-5MN32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2216-5MN32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2216-5MN32-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2216-5MN32-0HH0 is a 3-pole molded case circuit breaker (MCCB) designed specifically for motor protection, carrying a full-load amp rating of 160 A that holds flat across the entire 40 °C to 70 °C ambient range — no derating needed up to that ceiling. Breaking capacity is 121 kA at 415 V and 187 kA at 240 V, with a steep drop to 4.5 kA at 690 V, so the interrupting rating at your system voltage governs the panel SCCR calculation.

Physical integration

Maximum power loss is 19.7 W, so thermal dissipation inside a sealed enclosure needs to be checked against the panel's heat budget.

Frequently asked questions

What are the physical dimensions of this MCCB?

Depth is 86 mm, width is 105 mm, and height is 181 mm — a standard SENTRON 3VA frame size.

MPN
3VA2216-5MN32-0HH0