Siemens 3VA2216-6HL32-0AA0 SENTRON MCCB, 160 A, 242 kA at 24

MPN3VA2216-6HL32-0AA0
Active

Siemens SENTRON 3VA2216-6HL32-0AA0, molded case circuit breaker, 3-pole, 160 A continuous, ETU320 release, 242 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2216-6HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2216-6HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.19.7 W
3VA2216-6HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2216-6HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2216-6HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2216-6HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2216-6HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

At 415 V and 440 V it still interrupts 187 kA, dropping to 121 kA at 500 V and 4.5 kA at 690 V, so the SCCR planning has to track the actual system voltage.

The ETU320 release is a basic electronic trip unit (no communication, no ground-fault monitoring) suited for standard overload and short-circuit protection on feeders or large branch circuits. The 3-pole frame handles three-phase loads; the IP40 front protection means it lives in a clean panel, not a washdown zone.

Panel integration

The 86 mm depth fits typical distribution boards; leave clearance for cable entry and the ETU320 interface.

Frequently asked questions

Where can I buy 3VA2216-6HL32-0AA0 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an RFQ for your quantity.

What is the breaking capacity of 3VA2216-6HL32-0AA0 at different voltages?

242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V — plan SCCR coordination around the actual system voltage.

What compliance documentation does Siemens provide for this MCCB?

Standard Siemens documentation includes RoHS and REACH declarations; UL and IEC certifications are typical for the SENTRON 3VA series. Specific certificates available on request.

MPN
3VA2216-6HL32-0AA0