Skip to main content
Siemens 3VA2216-6HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2216-6HL42-0AA0 SENTRON MCCB, 160 A, 4-Pole, ETU3

MPN3VA2216-6HL42-0AA0
Active

Siemens SENTRON 3VA2216-6HL42-0AA0, molded case circuit breaker, 4-pole, 160 A continuous, ETU320 electronic trip unit, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2216-6HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2216-6HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.19.7 W

Protection & Trip Unit

3VA2216-6HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2216-6HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2216-6HL42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2216-6HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2216-6HL42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

160 A MCCB with ETU320 — what the ratings mean for your panel

The Siemens SENTRON 3VA2216-6HL42-0AA0 is a 4-pole molded case circuit breaker rated for 160 A continuous current at 40 °C through 70 °C — no derating needed across that band, which simplifies panel layout in warm enclosures. Its ETU320 electronic trip unit (line protection design) provides adjustable overload and short-circuit protection; the breaker carries a maximum breaking capacity of 242 kA at 240 V and 4.5 kA at 690 V. Rated insulation voltage is 800 V, and the front face carries IP40 protection — fine for a clean indoor panel, but not for washdown zones.

Physical fit — what ships in the carton

Dimensions are 181 mm high × 140 mm wide × 86 mm deep — a standard MCCB footprint for 160 A frame size, so it drops into existing 3VA panel cutouts without rework. No undervoltage release, no voltage trip, no communication module, no ground-fault monitoring — this is a straight line-protection breaker with the ETU320 as the only release. Maximum power loss is 19.7 W — factor that into your enclosure thermal budget if you're stacking several breakers in a sealed cabinet.

Frequently asked questions

Does the 3VA2216-6HL42-0AA0 include a ground-fault module?

No — this is the 'without' ground-fault monitoring version. It ships as a straight line-protection breaker with the ETU320 trip unit only.

MPN
3VA2216-6HL42-0AA0