Skip to main content
Siemens 3VA2216-6HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2216-6HN42-0AA0 SENTRON MCCB, 160 A, 4-Pole, ETU3

MPN3VA2216-6HN42-0AA0
Active

Siemens SENTRON 3VA2216-6HN42-0AA0, molded case circuit breaker, 4-pole, 160 A continuous rating, ETU350 electronic trip unit, breaking capacity 242 kA at 240 VAC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2216-6HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2216-6HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.19.7 W
3VA2216-6HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2216-6HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2216-6HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2216-6HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2216-6HN42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

160 A MCCB with ETU350 — line protection for high-fault panels

The Siemens SENTRON 3VA2216-6HN42-0AA0 is a 4-pole molded case circuit breaker rated for 160 A continuous current, built around the ETU350 electronic trip unit. It delivers a breaking capacity of 242 kA at 240 VAC and 187 kA at 415 VAC, which means it can safely interrupt fault currents up to those levels without cascading upstream — critical for high-fault-capacity main feeders or distribution panels where selective coordination matters. Rated insulation voltage is 800 V, and the breaker carries a full 160 A across the ambient range from 40 °C to 70 °C with no derating — a flat thermal curve that simplifies panel design in warm enclosures.

Dimensions are 181 mm high, 140 mm wide, and 86 mm deep — a standard SENTRON 3VA2 frame footprint. The 4-pole configuration covers three-phase-plus-neutral or three-phase with a switched neutral, depending on system design.

Frequently asked questions

Will 3VA2216-6HN42-0AA0 drop into a panel designed for 3VA1112-5EE32-0AA0?

No — the 3VA2 frame is larger (181 x 140 x 86 mm vs the 3VA1 frame), so the panel cutout and busbar arrangement would need modification.

MPN
3VA2216-6HN42-0AA0