Specifications

Identification

3VA2216-7MN32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2216-7MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2216-7MN32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.75 W

Protection & Trip Unit

3VA2216-7MN32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2216-7MN32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2216-7MN32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2216-7MN32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2216-7MN32-0BH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens SENTRON 3VA2216-7MN32-0BH0 is a 3-pole molded case circuit breaker (MCCB) in the motor protection version, rated for 160 A continuous current at 40 °C ambient. It carries a breaking capacity of 330 kA at 240 V, stepping down to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V — covering high-fault installations where SCCR headroom matters. The ETU350M overcurrent release provides adjustable thermal-magnetic protection tailored for motor loads, with phase failure detection built in. An undervoltage release (UVR) is integrated, and the auxiliary contact block includes 2 auxiliary switches plus a trip alarm switch (HQ configuration). Rated insulation voltage is 800 V, and the breaker dissipates up to 75 W at full load. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Mechanical endurance is rated at 20,000 operations.

Sourcing & Lifecycle

The integrated auxiliary trip (3VA9608-0BB11) and the supplied basic switch (3VA2216-7MN32-0AA0) are listed as companion components, ensuring replacement parts are traceable.

Integration Notes

Panel footprint: 105 mm wide × 181 mm high × 86 mm deep. The 3-pole form factor fits standard MCCB mounting in distribution boards or motor control centers. The undervoltage release and auxiliary contacts are factory-integrated, reducing field wiring. Phase failure detection is active via the ETU350M trip unit — no separate monitoring module needed. The trip indicator provides local visual status.

Frequently asked questions

Where can I buy 3VA2216-7MN32-0BH0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at different voltages?

Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V.

What overcurrent release does this breaker use?

It uses the ETU350M electronic trip unit, designed for motor protection with adjustable settings and phase failure detection.

What auxiliary contacts are included?

The breaker includes 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), plus an integrated undervoltage release.

MPN
3VA2216-7MN32-0BH0