Skip to main content
Siemens 3VA2216-7MN32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2216-7MN32-0HC0 SENTRON MCCB, 160 A, 3-Pole, Moto

MPN3VA2216-7MN32-0HC0

Siemens SENTRON 3VA2216-7MN32-0HC0, molded case circuit breaker, 3-pole, motor protection version, 160 A rated continuous current, ETU350M electronic trip unit, breaking capacity 330 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2216-7MN32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2216-7MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2216-7MN32-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.75 W

Protection & Trip Unit

3VA2216-7MN32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2216-7MN32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2216-7MN32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2216-7MN32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2216-7MN32-0HC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Motor protection MCCB with ETU350M — what the ratings mean for fit

The Siemens 3VA2216-7MN32-0HC0 is a SENTRON molded case circuit breaker configured specifically for motor protection, carrying a rated continuous current Iu of 160 A across a 3-pole frame. The ETU350M electronic trip unit provides adjustable overload and short-circuit protection curves matched to motor starting characteristics — meaning it tolerates the inrush without nuisance tripping while still clearing a locked-rotor fault. Breaking capacity runs from 330 kA at 240 V down to 52.5 kA at 690 V, so the same frame covers high-fault panels at lower voltages and standard industrial distribution at 400/480 V. Thermal derating is published from 40 °C through 70 °C: the breaker holds its full 160 A up to 50 °C, then steps down to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. If the panel ambient runs above 50 °C, that derating curve is the one that governs the real load — not the nameplate 160 A. Phase failure detection is built in, which is the main reason to pick the motor-protection version over a standard feeder MCCB — it catches a lost phase before the motor single-phases to failure. The auxiliary contact package comes as 2 HQ auxiliary switches, and a shunt trip (STL) release is fitted for remote tripping.

Panel integration — dimensions and mounting

The breaker measures 105 mm wide, 181 mm high, and 86 mm deep. It mounts on a DIN rail or can be screw-fixed to a backplate in the standard SENTRON 3VA footprint. The 86 mm depth is the projection from the mounting surface to the front of the breaker — relevant when sizing the gland plate clearance or door cutout. Maximum power loss is 75 W, so account for that heat in the enclosure thermal calculation, especially when grouping multiple breakers in a row.

Integrated components — basic switch and auxiliary trip

The breaker ships with a supplied basic switch 3VA2216-7MN32-0AA0 and an integrated auxiliary trip 3VA9688-0BL30. These are the internal switching elements that the ETU350M drives. If you are replacing a failed unit, verify that the replacement carries these same subcomponents — the order code encodes them, so ordering the full 3VA2216-7MN32-0HC0 ensures the correct match.

Frequently asked questions

Where can I buy 3VA2216-7MN32-0HC0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm commitment.

What is the breaking capacity of 3VA2216-7MN32-0HC0 at different voltages?

Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. These are the maximum fault currents the breaker can safely interrupt at each voltage level.

What is the thermal derating for 3VA2216-7MN32-0HC0?

The breaker carries 160 A continuously from 40 °C to 50 °C. Above 50 °C it derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C (–). The operating temperature range is -25 °C to +70 °C.

Does 3VA2216-7MN32-0HC0 include phase failure detection?

Yes, phase failure detection is built into the motor protection version. This is a standard feature of the ETU350M trip unit in the motor protection configuration.

MPN
3VA2216-7MN32-0HC0