Skip to main content
Siemens 3VA2216-7MS32-0AF0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2216-7MS32-0AF0 MCCB, 160A, 330kA at 240V

MPN3VA2216-7MS32-0AF0

SENTRON 3VA2216-7MS32-0AF0, molded case circuit breaker, 3-pole, 160 A, 330 kA at 240 V, starter protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2216-7MS32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Basic switch (supplied) ref.#BEZUG!
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2216-7MS32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V4.5 kA
Power loss, max.19.7 W
3VA2216-7MS32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
Overcurrent protection functionI
Ground-fault monitoringWithout
3VA2216-7MS32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2216-7MS32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2216-7MS32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2216-7MS32-0AF0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The SENTRON 3VA2216-7MS32-0AF0 is a 3-pole molded case circuit breaker (MCCB) in the starter protection version, rated for 160 A continuous current across the full -25 °C to 70 °C operating range.

What the interrupting ratings mean for panel coordination

At 415 V and 440 V the breaker interrupts 242 kA; at 500 V it clears 187 kA. Those numbers drop sharply at 690 V to 4.5 kA — a reminder that this MCCB is optimized for 240–500 V distribution, not 690 V motor circuits.

Physical fit and auxiliary contacts

Frequently asked questions

What is the interrupting capacity of 3VA2216-7MS32-0AF0 at 240 V?

330 kA at 240 V, which is the highest interrupting rating on this breaker and governs its use in high-fault utility feeds.

Where can I buy 3VA2216-7MS32-0AF0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2216-7MS32-0AF0