Skip to main content
Siemens 3VA2216-8KQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2216-8KQ32-0AA0 SENTRON MCCB, 160 A, 3-Pole, ETU8

MPN3VA2216-8KQ32-0AA0
Active

Siemens SENTRON 3VA2216-8KQ32-0AA0, molded case circuit breaker, line protection, 3-pole, 160 A, ETU860 electronic trip unit, 440 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2216-8KQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2216-8KQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.19.7 W

Protection & Trip Unit

3VA2216-8KQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860

Construction & Connection

3VA2216-8KQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2216-8KQ32-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2216-8KQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2216-8KQ32-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

What the ratings mean for fit

The Siemens SENTRON 3VA2216-8KQ32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current with no derating across the entire -40 °C to 70 °C operating range — that is the headline number for a BOM line. The 800 V rated insulation voltage (Ui) and the short-circuit breaking capacities — 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, 53 kA at 690 V — define where this breaker can be installed without cascading upstream. The ETU860 electronic trip unit provides adjustable time-delay settings (tr from 0.5 to 25 s, tsd up to 0.5 s) plus ground-fault monitoring via summation current formation, which means it can be coordinated downstream for selective tripping in a distribution panel.

Integration and deployment context

At 86 mm deep, 105 mm wide, and 181 mm tall, this MCCB fits standard Siemens SENTRON 3VA panel footprints and busbar systems. The IP40 front protection means it is suited for enclosed distribution boards where the front face is behind a panel door — not for open washdown environments. The communication function and other measurement function (both confirmed on this variant) allow integration into a higher-level monitoring system, so a controls integrator can pull trip and load data without separate metering.

Frequently asked questions

Where can I buy 3VA2216-8KQ32-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for volume or single-piece requirements.

What are the key ratings for 3VA2216-8KQ32-0AA0?

160 A continuous current with no derating up to 70 °C, 3-pole, 800 V rated insulation voltage, short-circuit breaking capacity of 440 kA at 240 V and 330 kA at 415 V, ETU860 electronic trip unit with adjustable time delays and ground-fault monitoring.

What is the depth of this MCCB?

The depth is 86 mm (3.4 in), with a width of 105 mm (4.1 in) and height of 181 mm (7.1 in).

What compliance documentation does Siemens provide for this part?

The part carries the DIN EN 81346-2 reference code Q, indicating it is classified as a switching device in power distribution. Standard Siemens MCCB documentation includes RoHS and REACH compliance declarations, and UL/IEC certifications are typical for the SENTRON 3VA series — verify specific certificate numbers against your project requirements.

MPN
3VA2216-8KQ32-0AA0