SENTRON 3VA2216-8KQ42-0AA0 MCCB, 160 A, 440 kA at 240 V

MPN3VA2216-8KQ42-0AA0
Active

SENTRON 3VA2216-8KQ42-0AA0, Molded case circuit breaker, 4-pole, 160 A continuous, 440 kA at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2216-8KQ42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2216-8KQ42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.19.7 W

Protection & Trip Unit

3VA2216-8KQ42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L + N conductor
Grounding protection functionYes

Construction & Connection

3VA2216-8KQ42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2216-8KQ42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2216-8KQ42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2216-8KQ42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

160 A MCCB with 440 kA interrupting capacity — the so-what for your panel

The SENTRON 3VA2216-8KQ42-0AA0 is a 4-pole molded case circuit breaker rated for 160 A continuous current and designed for line protection. Its interrupting capacity hits 440 kA at 240 V and 330 kA at 415 V — that SCCR headroom means it can sit upstream of a high-fault service entrance or a transformer secondary without cascading failure. The 160 A rating holds flat across the full ambient range from 40 °C to 70 °C (–), so no derating headache in a warm enclosure.

Selectivity and coordination — where the 3VA2216 earns its place

With a rated insulation voltage of 800 V and a maximum breaking capacity of 1 920 A, this MCCB is sized for main or feeder duty. The 4-pole construction handles three-phase plus neutral.

Panel integration — dimensions and mounting

The 3VA2216-8KQ42-0AA0 measures 181 mm high by 140 mm wide by 86 mm deep. That 140 mm width is a standard 4-pole MCCB footprint for a 160 A frame.

Communication and monitoring — built-in, not an add-on

This MCCB includes a communication function and an other measurement function. The maximum power loss is 19.7 W. No undervoltage release is fitted, and the trip indicator is not present.

Frequently asked questions

Does 3VA2216-8KQ42-0AA0 include ground-fault protection?

Yes, it has ground-fault monitoring via summation current formation on L + N conductor.

MPN