Skip to main content
Siemens 3VA2220-0MN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2220-0MN32-0AA0 SENTRON MCCB, 200 A, 3-Pole, ETU3

MPN3VA2220-0MN32-0AA0
Active

Siemens SENTRON 3VA2220-0MN32-0AA0, molded case circuit breaker, 3-pole, 200 A, ETU350M electronic trip unit, adjustable trip class 10A/10E/20E, 440 kA breaking capacity at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2220-0MN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2220-0MN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C200 A
Current at 60 °C200 A
Current at 65 °C200 A
Current at 70 °C200 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.46 W
3VA2220-0MN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2220-0MN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2220-0MN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2220-0MN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2220-0MN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens 3VA2220-0MN32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 200 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. That makes it a straight drop-in for a 200 A bus or feeder that sees warm enclosure temps without recalculating the wire size. It's built around the ETU350M electronic trip unit with adjustable trip classes 10A, 10E, and 20E, so it's specced for motor protection duty — the 10A class catches standard motor starts, and the 20E gives headroom for high-inertia loads like fans or centrifuges. Phase failure detection is onboard, which keeps a single-phased motor from cooking before the overload curve catches it. The 86 mm depth, 105 mm width, and 181 mm height fit the standard SENTRON 3VA footprint — same panel cutout as other 3VA breakers in this frame size.

Sourcing and lifecycle — still a current catalog line

No undervoltage release or shunt trip fitted from the factory — if you need UVR for a safety circuit or remote trip, that's an accessory add-on. No communication function onboard either; this is a standalone thermal-magnetic replacement with electronic trip, not a networked breaker.

Frequently asked questions

Where can I buy 3VA2220-0MN32-0AA0 and how do I get a price?

The 3VA2220-0MN32-0AA0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2220-0MN32-0AA0 at 415 V?

The 3VA2220-0MN32-0AA0 is rated for 440 kA breaking capacity at 415 V, and 187 kA at 690 V.

What trip classes are available on the 3VA2220-0MN32-0AA0?

The ETU350M trip unit offers adjustable trip classes 10A, 10E, and 20E, covering standard motor starts through high-inertia loads.

Does the 3VA2220-0MN32-0AA0 include phase failure detection?

Yes, phase failure detection is built into the ETU350M trip unit — it will trip on a lost phase to protect motor loads.

MPN
3VA2220-0MN32-0AA0