Three poles, adjustable trip class (10A, 10E, 20E), and phase failure detection are on board.
Short-circuit ratings that follow the voltage
The interrupting capacity drops as the line voltage rises — 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 5.2 kA at 690 V. That 121 kA at 415 V is the figure that matters for most European industrial panels; the 5.2 kA at 690 V means this frame is not the right choice for a 690 V bus unless the fault level is very low.
Motor protection trip classes
Adjustable trip class gives you 10A (fast — tight thermal protection for short-time overloads), 10E (standard motor start), or 20E (high-inertia loads like fans or centrifuges that need a longer acceleration ramp). The 200 A frame covers motor FLC from roughly 100 A up to the 200 A ceiling, depending on the OL setting range.
Panel fit
Footprint is 105 mm wide × 181 mm high × 86 mm deep — standard 3-pole MCCB envelope for a 200 A frame.