Breaking capacity reaches 187 kA at 240 V, dropping to 121 kA at 415 V, 75.6 kA at 500 V, and 5.2 kA at 690 V — the high 240 V figure suits it for North American 277/480 V wye systems where the line-to-ground fault current can be severe on the secondary side of a 1500 kVA transformer.
Dimensions are 105 mm wide × 181 mm tall × 86 mm deep — a standard SENTRON 3VA2 frame size that drops into the same mounting footprint as other 200 A SENTRON MCCBs, so a panel designed for a 3VA2 frame accepts this unit without re-drilling the backplate. Maximum power loss of 46 W at rated load — factor that into enclosure ventilation calculations if the panel is sealed; a 200 A breaker dumping 46 W into a small steel box can raise internal ambient above the 70 °C operating limit. Comes with 4 HQ auxiliary switches pre-installed (design of the auxiliary switch: 4 auxiliary switches HQ), so there is no separate add-on order for status feedback to the PLC or alarm annunciator.